1、 Scope of application: C65 circuit breaker accessories (MN undervoltage release, MV overvoltage release, MN+MV overvoltage release, SD alarm contact
Product details

Product Introduction

1、 Scope of application

C65 Circuit Breaker AccessoriesMN undervoltage release, MV overvoltage release, MN+MV overvoltage release, SD alarm contact, OF auxiliary contact are auxiliary functional components designed specifically for C65 circuit breakers. By providing overvoltage, undervoltage, and overvoltage detection to the power supply, they control the on/off of the circuit breaker, disconnect the distribution system circuit, or detect the circuit breaker signal. Can be used in conjunction with C65N, NB1 and other series circuit breakers.

2、 Model meaning and main technical parameters

product name model Rated working voltage Un drop away voltage Purpose:
Overvoltage release device MV 230V Overvoltage value Uvo=270V ± 5% When the power supply voltage rises between 270V ± 5%, the circuit breaker trips to achieve overvoltage protection of the line.
undervoltage release MN 230V Undervoltage value Uoe=170V ± 5% When the power supply voltage drops between 170V ± 5%, the circuit breaker trips to achieve under voltage protection of the line.
Overvoltage and undervoltage release device MV+MN 230V Overvoltage value Uvo=270V ± 5%
Undervoltage value Uoe=170V ± 5%
When the rated power supply voltage of 220V rises to 270 ± 5% or drops to 170V ± 5%, the circuit breaker will trip to achieve line protection.
Alarm contact SD 115/230/400V 1、3A When the circuit breaker is disconnected due to a fault in the protected circuit, provide an alarm signal
auxiliary contact OF 115/230/400V 1、3A Provide auxiliary signals and control auxiliary circuits

Attachment Name Rated insulation voltage Ui Rated control power supply voltage Us Release power consumption (W or VA) pull-in voltage
MX+OF shunt release+auxiliary contact 415V AC/DC: 220~380V; 110~220V 240 (0.7~1.1)Us
AC/DC:24~48V 120
MX+OF shunt release+auxiliary contact active 415V AC/DC: 220~380V; 110~220V 240 (0.7~1.1)Us
AC/DC:24~48V 120
passive 415V AC/DC: 220~380V; 110~220V 240 (0.7~1.1)Us
AC/DC:24~48V 120
MX shunt release 415V AC/DC: 220~380V; 110~220V 240 (0.7~1.1)Us
AC/DC:24~48V 120

Attachment Name Rated current (A) Number of contacts per group
AC:380V AC:220V DC:110V
Auxiliary contact OF 3 6 1 One normally open; A normally closed
Alarm contact SD 3 6 1 One normally open; A normally closed

3、 Appearance and installation dimensions


4、 Ordering Notice

When placing an order, please indicate the following points:
Product model and name: such asMV overvoltage release device
Supporting product: Chint NB1 circuit breaker matching
Order quantity: such as 3680 pieces.
Example of ordering:MN undervoltage release deviceC65 Circuit Breaker Accessories3990 of them.