The Rosemount 3051 series pressure transmitter is one of the series products of Rosemount Corporation's pressure transmitters that have been tested in the power industry for 40 years. A design with high reliability, long-term stability, and easy maintenance. The optimal measurement concept can be achieved from design to installation, maintenance to operation.
pressure range
0.075% reference accuracy from 0-1.5 psi to 0-4000 psi (from 0-10 to 0-27580 kPa), including linearity, hysteresis, and repeatability
Range ratio reaches 100:1
Lightweight and compact size help achieve easy installation and handling
Under actual process conditions, it can achieve a stability of 5 years
Performance Specifications
Zero based range, reference conditions, silicone oil filling solution, and 316L stainless steel isolation diaphragm. )
Reference accuracy
± 0.075% calibration range. The comprehensive effects include linearity, hysteresis, and repeatability.
For ranges with a range ratio less than 5:1, accuracy=± [0.025+(0.01) (URL/range)]% range
Environmental temperature impact
The overall impact is expressed as follows:
± (0.15% URL+0.15% range)/50 ° F (28 ° C)
The ambient temperature range is from -40 ° F to 185 ° F (-40 ° C to 85 ° C)
stability
For temperature changes of ± 50 ° F (28 ° C), reach ± 0.125% URL within 5 years.
vibration effect
Only considering the influence of resonance frequency, other vibration effects are ignored. Under resonance, a vibration of 15-2000 Hz is applied at any angle to the pipeline axis for testing, and the vibration effect is less than ± 0.1% URL/g
Power supply impact
Less than ± 0.01% calibrated range/volt
Installation location impact
Zero drift can reach 2.5 inH2O (63.5 mmH20), but it can be corrected. No range influence.
Radio frequency interference (RFI) impact
Less than ± 0.25% upper range limit (URL) (20-1000 MHz, 30 V/m, with piping for leads). Less than ± 0.25% range upper limit (URL) (20-1000 MHz, 10 V/m, using unshielded twisted pair, no piping).
Transient voltage protection limit
Compliant with IEEE C62.41, Class B
6 kV peak (0.5 μ s – 100 kHz)
3 kV peak (8 × 20 microseconds)
6 kV peak (1.2 × 50 microseconds)
Compliant with IEEE C37.90.1, shock resistance capability
SWC 2.5 kV peak, 1.25 MHz waveform
General technical specifications:
Response time:<1 nanosecond
Peak impulse current: 5000 A, for the casing
Peak transient voltage: 100 V DC
Loop impedance:<25 ohms
Applicable standards: IEC61000-4-4, IEC61000-4-5
Typical model of Rosemount 3051GP pressure transmitter:
3051GP1A2B21AB4M5
3051GP2A2B21AB4M5
3051GP3A2B21AB4M5
3051GP4A2B21AB4M5
3051GP5A2B21AB4M5
3051GP1A2B21AB4M5K5
3051GP2A2B21AB4M5K5
3051GP3A2B21AB4M5K5
3051GP4A2B21AB4M5K5
3051GP5A2B21AB4M5K5
3051GP1A2B21AB4M5E5
3051GP2A2B21AB4M5E5
3051GP3A2B21AB4M5E5
3051GP4A2B21AB4M5E5
3051GP5A2B21AB4M5E5
3051GP1A2B21AB4M5I5
3051GP2A2B21AB4M5I5
3051GP3A2B21AB4M5I5
3051GP4A2B21AB4M5I5
3051GP5A2B21AB4M5I5