Product details configuration
Customer Case
Xinyu Pharmaceutical Co., Ltd
Tongling Xinke Fine Chemical Co., Ltd
Anhui Ante Food Co., Ltd
Advantages of Stellar Seasons
20 Technology Sedimentation Casting Fine Star Seasons
20 years of production and manufacturing experience, 3 major production bases, 50000 square meters of production plants, fully automated production lines, national calibration and testing system, 108 production processes with strict quality control management to ensure that the quality of each product meets national quality standards
40 patented technologies save 30% energy
Jointly established a refrigeration system project design and research institute with the University of Science and Technology of China, with 4000 industry solution experiences, over 40 patented technologies, and energy savings of over 30% in operation
Professional technical team provides free solution design
A technical team of 20 people provides free targeted overall solutions for different enterprise project situations. According to enterprise needs, customized and reliable systems can be provided to safeguard enterprise production
Double after-sales service guarantee solves worries
7 × 24-hour after-sales service team, IoT mobile APP remote monitoring system, providing fault warning function to reduce the impact of equipment failure, lifetime warranty, and helping enterprise development
| Technical parameters of water-cooled maglev frequency conversion unit | ||||||||||
| type number 50STD-Model | F150WP1 | F300WP1 | F450WP1 | |||||||
| Nominal Refrigerating Capacity Rated cooling capacity |
×1000 kcAHl/h | 480.7 | 961.3 | 1442.0 | ||||||
| kW | 559 | 1118 | 1677 | |||||||
| USRT | 158.9 | 317.9 | 476.8 | |||||||
| input powerInput Power | kW | 94.8 | 189.6 | 284.4 | ||||||
| electricity source Power supply | 3φ-380V-50Hz | |||||||||
| protective device Protection Device | Reverse phase protection, phase loss protection, overcurrent protection, exhaust temperature protection, high and low voltage protection, low temperature protection, reserved water flow protection interface Phase Peversion Protection、Phase Lack Protection、Overload Current Protection、The Reserved Water Protection Interface |
|||||||||
| 制冷回路 Number of refrigeration circuits | 1 | |||||||||
| Energy control% Capacity control | 25%~100% | |||||||||
| refrigerant Refrigerant Charge(kg) |
R134a | |||||||||
| Condenser | Shell and Tube Type | |||||||||
| condenser Condenser |
Import and export pipe diameter Dia. Ov Pipe(inch) | 5″ | 6″ | 6″ | ||||||
| Maximum pressure on the water side Water Side Max Pressure (Mpa) | 1 | |||||||||
| Cooling water flow rate CoolingWater Folw (m3/h) |
112.4 | 224.9 | 337.3 | |||||||
| Water pressure drop Pressure drop(Kpa) | 72 | 75 | 77 | |||||||
| Evaporator | Full liquid Flooded Type | |||||||||
| evaporator Evaporator |
Import and export pipe diameter Dia. Ov Pipe(inch) | 5″ | 6″ | 6″ | ||||||
| Maximum pressure on the water side Water Side Max Pressure (Mpa) | 1 | |||||||||
| Frozen water flow rate Chilled Water Folw (m3/h) |
96.1 | 192.3 | 288.4 | |||||||
| Water pressure drop Pressure drop(Kpa) | 80 | 83 | 85 | |||||||
| Running noise Running noise dB(AH) | 68 | 69 | 70 | |||||||
| Total weight Total Weight(kg) | 2430 | 4600 | 6800 | |||||||
| operating weight Runnig weight(kg) | 2930 | 5100 | 7300 | |||||||
-
Note:
1. Nominal cooling capacity benchmark, ambient temperature of 35 ℃, chilled water outlet temperature of 7 ℃; Water flow rate 0.172m ³ (h/kW);
Dirt coefficient 0.088 ㎡·℃/kW;
2. Temperature range of frozen water: 5 ℃ -20 ℃
3. Minimum environmental range: 15 ℃ -40 ℃
4. Specification parameters and playability dimensions may change without prior notice due to product improvements.