The sensor part of the ZQ-LZ metal tube rotor flowmeter can be made of stainless steel (1Cr18Ni9Ti), molybdenum titanium (316, 316L), and lined with polytetrafluoroethylene materials. Special materials can also be used according to user requirements to adapt to flow measurement of corrosive fluids such as chlorine gas, salt water, hydrochloric acid, nitric acid, and sulfuric acid.
The YJF-YK-LZ metal tube rotor flowmeter adopts a variable area measurement principle and is used for continuous measurement of the volumetric flow rate of liquids and gases in closed pipelines. It has the characteristics of sturdy and reliable structure, wide temperature range, high accuracy, low price, and can be used for flow measurement in various occasions. This series is an on-site indicator type, with three installation forms: bottom in and top out, left in and right out, and bottom in and side out. It can be widely used for liquid and gas flow measurement in departments such as national defense, chemical industry, petroleum, metallurgy, power, environmental protection, medicine, and light industry.
The electric remote transmission metal tube float flowmeter outputs a standard current signal of 4-20mA, which can be used in conjunction with DDZ-II or DDZ-III electric unit combination instruments, or directly output to a computer system to participate in system monitoring. This instrument can be equipped with upper and lower limit alarms according to user needs.
1、 Measurement principle of metal tube rotor flowmeter:
|
The float of the ZQ-LZ metal tube rotor flowmeter is vertically installed inside the conical measuring tube. Due to the action of the fluid, it can move freely up and down in the conical tube. The outer diameter of the float and the annular area formed by the conical tube change with the position of the float. When the fluid flow rate stabilizes at a certain value, the float is also in a dynamic equilibrium state at a certain position, and the annular area between it and the conical tube remains constant. At this time, the float is subjected to three forces: the downward weight W of the float, the upward buoyancy F, and the dynamic force P of the fluid. These three forces reach equilibrium. According to the Bernoulli equation, force balance equation, and continuity theorem of fluid dynamics, the average instantaneous flow rate of fluid passing through the annular area can be calculated. |
|
2、 Main technical parameters:
|
1. Basic metal tube rotor flowmeter: (1) Measurement range: Water (20 ℃) 2.5-150000 L/h Air (20 ℃, 0.1013MPa) 0.07-4000Nm3/h; (2) Range ratio: 10:1; (3) Accuracy: 1.5/2.5; (4) Work pressure: ≤ 6.4MPa; (5) Working temperature: -40~350 ℃ (fluoroplastic lining -10~80 ℃); (6) Environmental temperature: -20~80 ℃; (7) Medium viscosity: DN15 ≤ 5mPa. S, DN25-DN150 ≤ 250mPa. S; (8) Tube material: 1Cr18Ni9Ti, 316L, lined with PTEF, etc; (9) Process connection: flange, or as provided by the user; (10) Steam jacket head: flange: DN15/PN1.6, or as provided by the user. |
2. Equipped with remote transmission metal tube rotor flowmeter: (1) Basic error: 1.5% F.S; (2) Output signal: 4-20mA; (3) Load impedance: 350 Ω; (4) Power supply voltage: 24V DC; (5) Environmental temperature: -30~80 ℃; (6) Outlet: M20 × 1.5; (7) Explosion proof mark: ExibIICT4;
|
3、 Outline dimension diagram of metal tube rotor flowmeter:
|
|
|
|
|
|
|
Bottom in, top out |
corrosion-resistant type |
Upward progress, downward exit |
Bottom in and side out |
Jacket type |
horizontal installation |
|
path (DN) |
L (mm) |
H (mm) |
B (mm) |
|
|
15 |
150 |
250 |
220 |
|
|
25 |
150 |
250 |
230 |
|
|
50 |
175 |
250 |
270 |
|
|
80 |
210 |
250 |
300 |
|
|
100 |
230 |
250 |
320 |
|
|
150 |
265 |
400 |
360 |
|
|
200 |
300 |
500 |
390 |
4、 Flow range table of metal tube float flowmeter:
|
Diameter (mm) |
Flow range |
Pressure loss kPa |
|||
|
Water L/h |
Air M3/h |
water |
air |
||
|
Conventional type |
corrosion-resistant type |
Conventional type, anti-corrosion type |
|||
|
DN15 |
2.5~25 |
--- |
0.07~0.7 |
6.5 |
7.1 |
|
4.0~40 |
2.5~25 |
0.11~1.1 |
6.5 |
7.2 |
|
|
6.3~63 |
4.0~40 |
0.18~1.8 |
6.6 |
7.3 |
|
|
10~100 |
6.3~63 |
0.28~2.8 |
6.6 |
7.5 |
|
|
16~160 |
10~100 |
0.40~4.0 |
6.8 |
8.0 |
|
|
25~250 |
16~160 |
0.7~7.0 |
7.2 |
10.8 |
|
|
40~400 |
25~250 |
1.0~10 |
8.6 |
10.0 |
|
|
63~630 |
40~400 |
1.6~16.0 |
11.1 |
14.0 |
|
|
DN25 |
100~1000 |
63~630 |
3~30 |
7.0 |
7.7 |
|
160~1600 |
100~1000 |
4.5~45 |
8.0 |
8.8 |
|
|
250~2500 |
160~1600 |
7~70 |
10.8 |
12.0 |
|
|
400~4000 |
250~2500 |
11~110 |
15.8 |
19.0 |
|
|
DN40 |
500~5000 |
--- |
12~120 |
10.8 |
9.8 |
|
600~6000 |
---- |
16~160 |
12.6 |
16.5 |
|
|
DN50 |
630~6300 |
400~4000 |
18~180 |
8.1 |
8.6 |
|
1000~10000 |
630~6300 |
25~250 |
11.0 |
10.4 |
|
|
1600~16000 |
1000~10000 |
40~400 |
17.0 |
15.5 |
|
|
DN80 |
2500~25000 |
1600~16000 |
60~600 |
8.1 |
12.9 |
|
4000~40000 |
2500~25000 |
80~800 |
9.5 |
18.5 |
|
|
DN100 |
6300~63000 |
4000~40000 |
100~1000 |
15.0 |
19.2 |
|
DN150 |
20000~100000 |
--- |
600~3000 |
19.2 |
20.3 |
5、 Installation diagram of metal tube float flowmeter:
6、 Selection table for metal tube rotor flowmeter:
|
ZQ-LZ |
Metal tube rotor flowmeter |
||||||||||||||
|
caliber (mm) |
15 |
DN15 |
80 |
DN80 |
|||||||||||
|
25 |
DN20 |
100 |
DN100 |
||||||||||||
|
40 |
DN40 |
150 |
DN150 |
||||||||||||
|
50 |
DN50 |
200 |
DN200 |
||||||||||||
|
structural form |
/ |
Bottom in, top out |
AA |
Side in, side out |
|||||||||||
|
H1 |
Left in, right out |
LA |
Low inlet side outlet |
||||||||||||
|
H2 |
Right in, left out |
S |
threaded installation |
||||||||||||
|
M |
Sanitary quick installation type |
||||||||||||||
|
body material |
R1 |
321 stainless steel |
RH |
Hastelloy C |
|||||||||||
|
R4 |
304 stainless steel |
RT |
Titanium |
||||||||||||
|
R6 |
316 stainless steel |
RF |
Stainless steel lined with PTFE |
||||||||||||
|
Indicator type |
7 |
Pointer displays instantaneous flow rate |
|||||||||||||
|
9 |
LCD displays instantaneous and cumulative |
||||||||||||||
|
Power supply and output signal |
K |
4~20mA DC24V |
|||||||||||||
|
Z |
4-20mA DC24V+HART protocol |
||||||||||||||
|
D |
Lithium battery powered with LCD meter head |
||||||||||||||
|
alarm output |
/ |
No alarm output |
|||||||||||||
|
1 |
Equipped with an alarm output |
||||||||||||||
|
2 |
Equipped with two alarm outputs |
||||||||||||||
|
measuring medium |
L |
liquid |
|||||||||||||
|
G |
gas |
||||||||||||||
|
Additional options |
T |
Measurement tube with insulation jacket |
|||||||||||||
|
B |
Explosion proof (ExII CT6) |
||||||||||||||